Subject: Re: Newly install generator 50kva with bad condition.
In-Reply-To: <DB9PR05MB9780A475AB5AD317CB5A0D66B33AA@DB9PR05MB9780.eurprd05.prod.outlook.com>
References: <AM8PR08MB645098E3187BE402E7172543993BA@AM8PR08MB6450.eurprd08.prod.outlook.com>
 <VI1PR05MB5342F768E671BE279A3D9631933BA@VI1PR05MB5342.eurprd05.prod.outlook.com>
 <DB9PR05MB97803525EE85C9E24C0A271EB33BA@DB9PR05MB9780.eurprd05.prod.outlook.com>
 <6814ca2b4ff4c14fdd057fa833c176ed@matech-cameroun.com>
 <AS4PR05MB94690A172F22717047021665F23BA@AS4PR05MB9469.eurprd05.prod.outlook.com>
 <VI1PR05MB53428F59A29980534BEB8E77933BA@VI1PR05MB5342.eurprd05.prod.outlook.com>
 <VI1PR05MB534269CD2297AF48CE32A366933AA@VI1PR05MB5342.eurprd05.prod.outlook.com>
 <AM8PR05MB723603C115EF49C7C557D6C8EF3AA@AM8PR05MB7236.eurprd05.prod.outlook.com>
 <DB9PR05MB9780A475AB5AD317CB5A0D66B33AA@DB9PR05MB9780.eurprd05.prod.outlook.com>
Message-ID: <fe432fe4b9abf00c8a4daa2cd460cfcc@matech-cameroun.com>
X-Sender: amza.njatono@matech-cameroun.com
Content-Type: text/plain; charset=UTF-8;
 format=flowed
Content-Transfer-Encoding: 8bit

Bonjour Patrice,

Bien vouloir préparer une batterie originale de 90 ou 100ah nous 
mettrons un technicien a disposition pour une descente sur site.

Le standard de garantie groupe électrogène brand new c'est un an ou 
1000h, une extension à 2000 heures c'est sous conditions de services 
supplémentaires de contrôle de l'exploitation.

Nous allons clarifier ensemble les conditions de garantie évoqué même 
puisque nous nous sommes accordés sur un projet low cost avec divers 
récupérations , et ne sauront couvrir les retours des opérations par 
manipulations partie prenante non qualifié.

Cordialement

Amza NJATONO
MATECH SARL


Le 2025-08-29 10:18, Patrick Esuma a écrit :
> Hello Amza,
> 
>  Les tests ont bien été effectués dans votre Warehouse ainsi que
> dans le notre.
> 
>  Malheureusement une fois installé dans le site le Gen n'a pas
> performé comme attendu par les Opérations
> 
>  Nous tenons à vous rappeler que tous les Gen issus de votre atelier
> bénéficient d'une garanti de 2000H après son installation dans le
> site. Nous vous prions d'envoyer votre équipe dans le site pour
> correction ou de faire revenir ce Gen dans votre Atelier pour une
> possible revision.
> 
>  Best Regards.
> 
> -------------------------
> 
>  From: Valeur Houell <valeur.houell@ihstowers.com>
> Sent: Friday, August 29, 2025 10:10 AM
> To: Sani Njamo <sani.njamo@ihstowers.com>; Stephane Ketchouang
> <stephane.ketchouang@ihstowers.com>; amza.njatono@matech-cameroun.com
> <amza.njatono@matech-cameroun.com>; Patrick Esuma
> <patrick.esuma.ctr@ihstowers.com>
> Cc: Ibrahim Mefire <ibrahim.mefire@matech-cameroun.com>; Astrid
> Chigheng Djouassi <astrid.djouassi@ihstowers.com>; Vensa Mohamadu
> <vensa.mohamadu@ihstowers.com>; Hugues Tchagou
> <hugues.tchagou@ihstowers.com>; Francois J. Nsegbe
> <francois.nsegbe@ihstowers.com>
> Subject: RE: Newly install generator 50kva with bad condition.
> 
> Hi Sani,
> 
> Call for a meeting to have the point discussed and way forward
> identified.
> 
> Best regards
> 
>  Valeur Houell Issey
> 
> Senior Manager, Operations
> 
> Mobile: +237 677549884
> 
>                +237 655999884
> 
> From: Sani Njamo <sani.njamo@ihstowers.com>
> Sent: Friday, 29 August 2025 09:45
> To: Stephane Ketchouang <stephane.ketchouang@ihstowers.com>;
> amza.njatono@matech-cameroun.com; Patrick Esuma
> <patrick.esuma.ctr@ihstowers.com>
> Cc: Ibrahim Mefire <ibrahim.mefire@matech-cameroun.com>; Astrid
> Chigheng Djouassi <astrid.djouassi@ihstowers.com>; Valeur Houell
> <valeur.houell@ihstowers.com>; Vensa Mohamadu
> <vensa.mohamadu@ihstowers.com>; Hugues Tchagou
> <hugues.tchagou@ihstowers.com>; Francois J. Nsegbe
> <francois.nsegbe@ihstowers.com>
> Subject: Re: Newly install generator 50kva with bad condition.
> 
> Hi Amza
> 
> No response from you
> Please note that this site carry 14 sites.
> 
>  Best regards
> 
> -------------------------
> 
> From: Sani Njamo <sani.njamo@ihstowers.com>
> Sent: Thursday, August 28, 2025 1:52 PM
> To: Stephane Ketchouang <stephane.ketchouang@ihstowers.com>;
> amza.njatono@matech-cameroun.com <amza.njatono@matech-cameroun.com>;
> Patrick Esuma <patrick.esuma.ctr@ihstowers.com>
> Cc: Ibrahim Mefire <ibrahim.mefire@matech-cameroun.com>; Astrid
> Chigheng Djouassi <astrid.djouassi@ihstowers.com>; Valeur Houell
> <valeur.houell@ihstowers.com>; Vensa Mohamadu
> <vensa.mohamadu@ihstowers.com>; Hugues Tchagou
> <hugues.tchagou@ihstowers.com>; Francois J. Nsegbe
> <francois.nsegbe@ihstowers.com>
> Subject: Re: Newly install generator 50kva with bad condition.
> 
> Bonsoir Amza
> 
> Ce générateur a été installé pour la première fois hier sur site
> et il y a accès de carburant .
> 
> Il serait préférable que vous envoyiez une équipe sur place.
> 
> C'est un Doyen qui a installe ce générateur et je n'ai aucun doute
> quant à sa compétence.
> 
> Best regards
> 
> -------------------------
> 
> From: Stephane Ketchouang <stephane.ketchouang@ihstowers.com>
> Sent: Thursday, August 28, 2025 10:50 AM
> To: amza.njatono@matech-cameroun.com
> <amza.njatono@matech-cameroun.com>; Patrick Esuma
> <patrick.esuma.ctr@ihstowers.com>
> Cc: Ibrahim Mefire <ibrahim.mefire@matech-cameroun.com>; Astrid
> Chigheng Djouassi <astrid.djouassi@ihstowers.com>; Valeur Houell
> <valeur.houell@ihstowers.com>; Vensa Mohamadu
> <vensa.mohamadu@ihstowers.com>; Hugues Tchagou
> <hugues.tchagou@ihstowers.com>; Sani Njamo <sani.njamo@ihstowers.com>;
> Francois J. Nsegbe <francois.nsegbe@ihstowers.com>
> Subject: RE: Newly install generator 50kva with bad condition.
> 
> @sani,
> 
> Bien vouloir répondre a la requête ci-dessous.
> 
>  Best Regards.
> 
> WEGNE KETCHOUANG Joel Stephane
> Manager, Operations
> 
> IHS Cameroon S.A.
> 1602/1606, Blvd. de La Liberté, Akwa
> P.O. Box 15115, Douala
> Cameroon
> www.ihstowers.com [1]
> Office: +237 242738708
> Mobile: +237677548354 / +237655999806
> Email: stephane.ketchouang@ihstowers.com
> 
> -----Original Message-----
> From: amza.njatono@matech-cameroun.com
> <amza.njatono@matech-cameroun.com>
> Sent: Thursday, 28 August 2025 10:11
> To: Patrick Esuma <patrick.esuma.ctr@ihstowers.com>
> Cc: Ibrahim Mefire <ibrahim.mefire@matech-cameroun.com>; Astrid
> Chigheng Djouassi <astrid.djouassi@ihstowers.com>; Stephane Ketchouang
> <stephane.ketchouang@ihstowers.com>; Valeur Houell
> <valeur.houell@ihstowers.com>; Vensa Mohamadu
> <vensa.mohamadu@ihstowers.com>; Hugues Tchagou
> <hugues.tchagou@ihstowers.com>; Sani Njamo <sani.njamo@ihstowers.com>;
> Francois J. Nsegbe <francois.nsegbe@ihstowers.com>
> Subject: Re: Newly install generator 50kva with bad condition.
> Importance: High
> 
> CAUTION: This email originated from outside of the organization. Do
> not click links or open attachments unless you recognize the sender
> and know the content is safe.
> 
> Bonjour Patrick ;
> 
> Bien vouloir partager les évidences compteur horaire et les
> différents point relevés.
> 
> Ces Groupes sortis de nos ateliers ont toutes les évidences
> d'overhaul , et sont complètement testé de manière rude dans votre
> Warehouse couronné d'une fiche de test qui prend habituellement toute
> une journée , tous les points que tu as cité étant mis en revue
> (TEMP , SENSORS , LOAD ) .
> 
> Maintenant pour simplifier ils accusent par exemple la pompe
> d'injection ,
>   y'a t'il eu panne sèche et prise d'air?
>   Ils l'ont géré comment , ils savent le faire?
> 
> Habituellement dans les projets énergie il faut être transparent
> pour aller vite , et vous voyez cette transparence de notre part dans
> tout le process des travaux.
> 
> Cordialement
> 
>   MATECH SARL
> 
> Le 2025-08-28 09:28, Patrick Esuma a écrit :
>> Hello @Ibrahim Mefire,
>> 
>>  Le Gen ELCOS 50 KVA sorti de votre atelier ne performe pas dans le
>> site.
>>  Après environ 2 heures de marche il s'est arrété avec l'alarme
> High
>> Temp. les ingénieurs sur site nous font les observations
>> suivantes:
>> 
>>       *
>> Le moteur chauffe anormalement
>>       *
>> La pompe à injection ne fonctionne pas normalement
>>       *
>> Certains capteurs sont en défauts.
>> 
>>  Nous sommes informés qu'il s'agit d'un site de haute priorité,
>> l'absence de ce Gen comme support power entrainerait une forte
>> instabilité et d'énormes pénalités.
>>  Nous vous prions de prendre rapidement des mesures pour apporter
> une
>> réponse corrective aux problèmes remontés.
>> 
>>  Bien vouloir entrer directement en contact avec @Sani Njamo
>> (+237677549819' +237655999819) et @Francois J. Nsegbe (+237683859238
>> '+237656072685), et partagez avec nous votre plan d'action.
>> 
>>  Best Regards.
>> 
>> -------------------------
>> 
>>  From: Sani Njamo <sani.njamo@ihstowers.com>
>> Sent: Thursday, August 28, 2025 8:21 AM
>> To: Patrick Esuma <patrick.esuma.ctr@ihstowers.com>
>> Cc: Astrid Chigheng Djouassi <astrid.djouassi@ihstowers.com>;
> Stephane
>> Ketchouang <stephane.ketchouang@ihstowers.com>; Valeur Houell
>> <valeur.houell@ihstowers.com>; Vensa Mohamadu
>> <vensa.mohamadu@ihstowers.com>; Hugues Tchagou
>> <hugues.tchagou@ihstowers.com>; Francois J. Nsegbe
>> <francois.nsegbe@ihstowers.com>
>> Subject: Fw: Newly install generator 50kva with bad condition.
>> 
>>  Hi @Patrick Esuma
>>  Below,The  report of newly Gen 50KVa ( Gen refurbished by Mateck )
>> installled at Buea Service center + 14  Your support is urgently
>> Needed
>> 
>>  Best regards
>> 
>> -------------------------
>> 
>>  From: Charles Obat Tatazoh <cobat@ieng-group.com>
>> Sent: Thursday, August 28, 2025 7:23 AM
>> To: Sani Njamo <sani.njamo@ihstowers.com>
>> Cc: Stephane Ketchouang <stephane.ketchouang@ihstowers.com>; Nasser
>> Tchagna Pondja <npondja@ieng-group.com>; Bachille
>> <bachille@ieng-group.com>; Kameni <ykameni@ieng-group.com>; Francois
>> J. Nsegbe <francois.nsegbe@ihstowers.com>; jtchouape
>> <jtchouape@ieng-group.com>
>> Subject: Newly install generator 50kva with bad condition.
>> 
>>  CAUTION: This email originated from outside of the organization. Do
>> not click links or open attachments unless you recognize the sender
>> and know the content is safe.
>> 
>>  Hello Sani.
>> 
>>  After installing the generator 50kva at Buea service center the
>> condition in wish I found this generator make me to test it.
>> 
>>  So, I decided to switch off grid and leave the site on generator
>> before going to mile 16 bolifamba.
>> 
>>  On my way back. about close to two hours, I found out that the
>> generator has stop and the site is on battery with the alarm of high
>> temperature.
>> 
>>  So, i try to control the engine thermometers in wish it has already
>> being remove even to start you have to kick it three time before it
>> can start.
>> 
>>  For my conclusion, this generator is poorly refurbished, and it
>> cannot work for a backbone site with this condition.
>> 
>>  Best
>> 
>>  Regards.
>> 
>>  Obat
>> 
>>  Charles Tatazoh
>> 
>>  O&M Coordinator(Generator)
>> 
>>  ieng Cameroon Sarl
>> 
>>  T : +237 233 425 514
>> 
>>  M: +237 677 54 8364
>> 
>> 
>> 
> https://urldefense.com/v3/__http://www.ieng-group.com__;!!L1krvcqbmg!Z
> [2]
>> 
> aN6n60vL5v4k7I29InSnC0l2x9XSpmxUlNvkt8XVDmJPCqCtwRB3JgOEekwezOh2yhLQbQ
>> CDXNF2f46g6jxQTFQqND0-PK8Co6TgqcE$  [1]
>> 
>> 
>> 
>> Links:
>> ------
>> [1]
>> 
> https://urldefense.com/v3/__http://www.ieng-group.com/__;!!L1krvcqbmg!