Return-Path: <amza.njatono@matech-cameroun.com>
Received: from node32-ca.n0c.com
	by node32-ca.n0c.com with LMTP
	id OIAIEgkLnGnfLjEA9IX2vw
	(envelope-from <amza.njatono@matech-cameroun.com>); Mon, 23 Feb 2026 08:08:41 +0000
Received: from 127.0.0.1 (unknown [10.123.3.49])
	by node32-ca.n0c.com (Postfix) with ESMTPA id E66A084E69;
	Mon, 23 Feb 2026 08:08:40 +0000 (UTC)
DMARC-Filter: OpenDMARC Filter v1.4.1 node32-ca.n0c.com E66A084E69
Authentication-Results: node32-ca.n0c.com; dmarc=fail (p=none dis=none) header.from=matech-cameroun.com
Authentication-Results: node32-ca.n0c.com; spf=fail smtp.mailfrom=matech-cameroun.com
DKIM-Filter: OpenDKIM Filter v2.11.0 node32-ca.n0c.com E66A084E69
DKIM-Signature: v=1; a=rsa-sha256; c=relaxed/relaxed; d=matech-cameroun.com;
	s=default; t=1771834120;
	bh=lNF58H7/JF0CpERia+LE420GnFQLrT3Y6HI/RBbHzms=;
	h=Date:From:To:Cc:Subject:In-Reply-To:References:From;
	b=aPbtMSaYjBr2ZOPqU3iArmq8S2XpfiAZzWNLb7rNM/zJPZP6tsSBaWWxja6p3MgaJ
	 hPPQOL+XvCoDNhLjsAQsUxxJQp9S+Jz/7ZWQ9oGkJyTLXfvm+BDed4U/d0XN2drU9v
	 exIXoe/TmWPkv7rEWmoFLe6U35krPuVu7bgCurOs=
MIME-Version: 1.0
Date: Mon, 23 Feb 2026 09:08:40 +0100
From: amza.njatono@matech-cameroun.com
To: jules.sagwa@matech-cameroun.com
Cc: andre.eko@matech-cameroun.com, 'Herve Iroume'
 <herve.iroume@matech-cameroun.com>, judicael.batchagnia@matech-cameroun.com
Subject: Re: NTUI generator faulty
In-Reply-To: <002101dca498$15a2d750$40e885f0$@matech-cameroun.com>
References: <DB9PR05MB76894E24AFAD439E43ED078A9869A@DB9PR05MB7689.eurprd05.prod.outlook.com>
 <8946cdc522b62894e72ed4d0eb26871e@matech-cameroun.com>
 <002101dca498$15a2d750$40e885f0$@matech-cameroun.com>
Message-ID: <6ffa415ee7cf6135172bd9a6ab4b7af2@matech-cameroun.com>
X-Sender: amza.njatono@matech-cameroun.com
X-Priority: 1 (Highest)
Content-Type: text/plain; charset=UTF-8;
 format=flowed
Content-Transfer-Encoding: 8bit

Bonjour,

J'ai demandé depuis de faire la liste des groupes de plus de 22000 
heures et soumettre au remplacement, ça aiderait même le Parc à avoir 
des solutions de remplacement et garder un parc solide, ça n'a jamais 
été fait.

Dans leur plainte il disent que vous cassez les moteurs, ils ont parlé 
de konkarack qui n'a pas fait Six mois en le remplaçant aviez vous 
l'historique passé ? Avait t'il été révisé pour tenir définitivement ?

Ils ont parlé de Nyom et des autres que vous maîtrisez, ils ont accusé 
la maintenance de Ntui en parlant de sanctions au techniciens qui 
cassent des moteurs.

Sauf que pour le cas de ntui qui est disparate si la qualité de 
maintenance est mauvaise ce cluster ne peut être maîtrisé.

Ils font le copié collé avec les autres sbc pourtant ce n'est ni les 
mêmes ressources ni la même politique.

Sincèrement trouvez un moyen de nous éviter d'être toujours entrain de 
prendre des coups en fonction de leur humeur, sortez une liste de 
groupes à mettre hors tu parc et soumettez par mail pour qu'ils se 
mettent aussi face à leurs responsabilités.

C'est contractuel.
Pour Les les groupes de secours également contractuel à 10.000 par jour 
mais aucune puissance n'est pas définie dans le contrat , il n'y a que 
le kipor 7500 ou le Total 7500 essence qui essaie rentrer dans ce budget 
même à perte.

Le 2026-02-23 08:43, jules.sagwa@matech-cameroun.com a écrit :
> Bonjour à tous.
> 
> A la suite de cet incident, Le RM IHS convoque une réunion de crise
> à son bureau jeudi le 26/02/2026 à 8 Heure.
> 
> Cordialement
> 
> SAGWA TCHOUPE
> 
> Data manager
> 
> Mobile : +237 676789251
> 
>                  +237 694025988
> 
> From: andre.eko@matech-cameroun.com <andre.eko@matech-cameroun.com>
> Sent: Sunday, February 22, 2026 9:11 PM
> To: Vensa Mohamadu <vensa.mohamadu@ihstowers.com>
> Cc: 'Amza Njatono' <amza.njatono@matech-cameroun.com>; Valeur Houell
> <valeur.houell@ihstowers.com>; Alphonse K. Deufo
> <alphonse.deufo@ihstowers.com>; Bate Agbor <bate.agbor@ihstowers.com>;
> Herve Iroume <herve.iroume@matech-cameroun.com>; Judicael Batchagnia
> <judicael.batchagnia@matech-cameroun.com>; Jules Sagwa
> <jules.sagwa@matech-cameroun.com>; Ibrahim Mefire
> <ibrahim.mefire@matech-cameroun.com>
> Subject: Re: NTUI generator faulty
> Importance: High
> 
> Bonsoir Vensa,
> 
> Le générateur a fait l’objet de toutes les maintenances
> préventives requises.
> A la survenance du problème notre équipe, est descendue sur site
> démontée la partie haute pour libérer le moteur sans succès. Ce
> qui démontre que le moteur est bloqué dans les parties basses. Les
> démontages complets ne se font généralement pas sur le terrain
> l’équipe n’avait pas les outils nécessaires pour déposer le
> moteur. Voir le rapport d’incident en attache.
> Nous avons eu 02 alarmes HT sur ce générateur due a la durite
> percée qui a été remplacée par la suite.
> Ce générateur a actuellement un compteur 8865 H il aurait du avoir
> une révision de sa partie haute et basse a 7000 h on procède au
> remplacement des joints de cache culbuteur, réglage des culbuteurs,
> remplacement des joints de queue.
> Nous allons poursuivre avec le démontage de la partie basse et vous
> adresser une cotation pour la remise en état de marche
> 
> Bien Cordialement
> -
> André Patrick EKO
> Directeur des Operations
> MATECH SARL
> 
> Tel: (+237) 656 298 031
> Mail: andre.eko@matech-cameroun.com
> 
> BP 5014, Douala
> Siege Social: Rue PAU AKWA DOUALA
> Showroom à AKWA, Carrefour Idéal
> Web: www.matech-cameroun.com [1]
> 
> Le 2026-02-21 10:28, Vensa Mohamadu a écrit :
> 
>> Hi Amza,
>> 
>> As discussed, this site is down due to faulty generator. Kindly
>> share
>> your plan to restore the service. We also want a RCA of this
>> incident.
>> 
>> IHS ID
>> 
>> Tenant Site ID
>> 
>> Site Name
>> 
>> Priority
>> 
>> outage Start Time
>> 
>> outage End Time
>> 
>> MTTR
>> 
>> Feedback//Resolution
>> 
>> IHS_YND_403
>> 
>> T1614
>> 
>> NTUI TOWN
>> 
>> P2
>> 
>> 20/02/2026 00:35
>> 
>> 20/02/2026 09:39
>> 
>> 09:03:30
>> 
>> Grid outage, Gen failed to start due to fuel shortage // refueling
>> done
>> 
>> IHS_YND_403
>> 
>> T1614
>> 
>> NTUI TOWN
>> 
>> P2
>> 
>> 19/02/2026 15:15
>> 
>> 19/02/2026 15:25
>> 
>> 00:09:23
>> 
>> IHS_YND_403
>> 
>> T1614
>> 
>> NTUI TOWN
>> 
>> P2
>> 
>> 19/02/2026 14:17
>> 
>> 19/02/2026 14:19
>> 
>> 00:01:52
>> 
>> Site went down because 03/03 rectifier hanging on site//Site
>> stabilised
>> 
>> IHS_YND_403
>> 
>> T1614
>> 
>> NTUI TOWN
>> 
>> P2
>> 
>> 08/02/2026 19:01
>> 
>> 08/02/2026 19:29
>> 
>> 00:28:45
>> 
>> Grid outage gen start and stopped due to overheating causing by hose
>> burst//we change hose and gen manually started
>> 
>> IHS_YND_403
>> 
>> T1614
>> 
>> NTUI TOWN
>> 
>> P2
>> 
>> 08/02/2026 00:02
>> 
>> 08/02/2026 02:30
>> 
>> 02:27:36
>> 
>> Grid gen gen start and stopped due to overheating causing by hose
>> burst//we add water ans gen manually
>> 
>> Regards,
>> 
>> Vensa MOHAMADU
>> 
>> Manager, Operations
>> 
>> Mobile: +237 677549843
>> 
>> +237 655999843amz
> 
> 