Return-Path: <info@matech-cameroun.com>
Delivered-To: dominique.djoum@matech-cameroun.com
Received: from node32-ca.n0c.com
	by node32-ca.n0c.com with LMTP
	id sFNPND/ILmk+1ysA9IX2vw
	(envelope-from <info@matech-cameroun.com>)
	for <dominique.djoum@matech-cameroun.com>; Tue, 02 Dec 2025 11:06:39 +0000
Received: from 127.0.0.1 (unknown [10.123.3.49])
	by node32-ca.n0c.com (Postfix) with ESMTPA id 85F9184E75;
	Tue,  2 Dec 2025 11:06:39 +0000 (UTC)
DMARC-Filter: OpenDMARC Filter v1.4.1 node32-ca.n0c.com 85F9184E75
Authentication-Results: node32-ca.n0c.com; dmarc=fail (p=none dis=none) header.from=matech-cameroun.com
Authentication-Results: node32-ca.n0c.com; spf=fail smtp.mailfrom=matech-cameroun.com
DKIM-Filter: OpenDKIM Filter v2.11.0 node32-ca.n0c.com 85F9184E75
DKIM-Signature: v=1; a=rsa-sha256; c=relaxed/relaxed; d=matech-cameroun.com;
	s=default; t=1764673599;
	bh=Mf9mFGqd4Qd7VKP+uSmRe+mfdoJNMpApajVVqhT7cEM=;
	h=Date:From:To:Cc:Subject:In-Reply-To:References:From;
	b=Dof3zVHvcnq0poHiDKHkTLf4lTmseK7tzIaCeBiYqOf55WdoV4mA3aZK5WdPwwYK9
	 udmH1eJJXSnfgcdZEoH8oAPdEHqbZ0GAFdpyaHx3U/E4oUAAP09P0s3YqtqgXK73Bb
	 YycO01J9wEjXDL8lVa1iCi06/j114UlHTuh6XvcY=
MIME-Version: 1.0
Date: Tue, 02 Dec 2025 12:06:39 +0100
From: info@matech-cameroun.com
To: "Tender Box, IHS Cameroon" <tenderbox.ihscameroon@ihstowers.com>
Cc: Dominique Djoum <dominique.djoum@matech-cameroun.com>
Subject: Re: RFQ for the supply of 200 DC Box - technical evaluation results
In-Reply-To: <PA6PR05MB119233B5B0185D80734A7E42982DBA@PA6PR05MB11923.eurprd05.prod.outlook.com>
References: <b2366fb38fa7737e5c6102fbb863f893@matech-cameroun.com>
 <PA6PR05MB119233B5B0185D80734A7E42982DBA@PA6PR05MB11923.eurprd05.prod.outlook.com>
Message-ID: <be763547a3e3df072c956c697410c916@matech-cameroun.com>
X-Sender: info@matech-cameroun.com
Content-Type: text/plain; charset=UTF-8;
 format=flowed
Content-Transfer-Encoding: 8bit

Dear sir/Madam

well recieved , will get back for you with  updated DC BOX

Regards

MATECH SARL


Le 2025-12-01 14:30, Tender Box, IHS Cameroon a écrit :
> Dear supplier,
> 
> Kindly consider below comments and update your offer.
> 
> Please share the filled datasheet initially transmitted (attached).
> 
> RESULTS: The technical specifications for this item have not been
> approved for the following reasons:
> 
>  1.                The circuit breakers technical datasheet and
> technical specification form not provided.
> 
>  2.                The copper busbar position does not conform.
> 
>  3.                Two pairs x 35sqmm are not compliant (color).
> 
>  4.                The copper busbar mounting points are not
> compliant, the connection point rod must be screwed onto the threaded
> bar to prevent an electric arc (risk of burns and loss of circuit
> breaker) and ensure a solid contact.
> 
>  5.                DCDB dimensions is not compliant.
> 
>  6.                Cable Glang position is not compliant(does not
> facilitate movement for handling and connecting power cables)
> 
> Br/
> 
> From: Dominique Djoum <dominique.djoum@matech-cameroun.com>
> Sent: Tuesday, 25 November 2025 15:39
> To: Tender Box, IHS Cameroon <tenderbox.ihscameroon@ihstowers.com>
> Cc: MATECH SARL <info@matech-cameroun.com>
> Subject: RFQ for the supply of 200 DC Box
> 
> CAUTION: This email originated from outside of the organization. Do
> not click links or open attachments unless you recognize the sender
> and know the content is safe.
> 
> Good evening,
> 
> Please find attached the offer relating to your request mentioned in
> the subject line.
> 
> A sample will be delivered to you shortly at the procurement office.
> 
> Respectueusement / Best Regards.
> --
> DOMINIQUE DJOUM
> Département Administratif et Comptable
> MATECH SARL
> 
> Tel: (+237) 692 76 67 37
> Mail: dominique.djoum@matech-cameroun.com
> 
> BP 5014, Douala
> Siege Social: Rue PAU AKWA DOUALA
> Showroom à AKWA, Carrefour Idéal
> Web: www.matech-cameroun.com [1]
> 
> 
> 
> Links:
> ------
> [1] http://www.matech-cameroun.com/