MIME-Version: 1.0
Date: Mon, 10 Aug 2026 11:06:02 +0100
From: herve.iroume@matech-cameroun.com
To: amza.njatono@matech-cameroun.com, Vensa Mohamadu
 <vensa.mohamadu@ihstowers.com>, Valeur Houell <valeur.houell@ihstowers.com>,
 Bate Agbor <bate.agbor@ihstowers.com>, Andre Eko
 <andre.eko@matech-cameroun.com>
Subject: Re: Fwd: LONG OUTAGE at Ebeba
 (NOCINC0008649666/Center/CTR_116/IHS_YND_339/P4/Grid-Gen-Lithium/MATECH)//
 BOTH OPERATORS
In-Reply-To: <2ee0af6ff1ad4572cb6218667060d042@matech-cameroun.com>
References: <DU4PR05MB123582A0E971613B4118A80A798DE2@DU4PR05MB12358.eurprd05.prod.outlook.com>
 <2ee0af6ff1ad4572cb6218667060d042@matech-cameroun.com>
Message-ID: <27da703695b6d3cfaa75fbd6d95c808f@matech-cameroun.com>
X-Sender: herve.iroume@matech-cameroun.com
Content-Type: text/plain; charset=UTF-8;
 format=flowed
Content-Transfer-Encoding: 8bit

Bonjour à tous.
Suite au mail de Mr Vensa concernant le site de Ebeba hier, le problème 
ne concerne pas la pompe d'injection à cassette du groupe.
Le problème vse trouve au niveau de la régulation de la pompe.
Je m'explique: la tringlerie qui agit sur la pompe est bloqué ce qui 
rend impossible l'ouverture du circuit de gasoil , empêchant ainsi le 
démarrage du groupe électrogène.
C'est vrai que ce défaut vous faire croire au départ que la pompe est 
bloqué.
C'est après avoir déposé la pompe que vous vous rendrez compte que le 
problème ne vient pas de la pompe.
Alors pour solutionner le problème, nous avons besoin d'un moteur 
similaire pour y prélever cet ensemble , et remonter sur le groupe de 
Ebeba.
Nous sommes dans l'attente d'un groupe que vous allez nous présenter 
pour faire cette opération.
Merci pour votre bonne compréhension et excellente début de semaine à 
tous.

-- 
Jean Herve Iroume

DOA

herve.iroume@matech-cameroun.com

Tel:659 906 629

        697 335 400