Return-Path: <herve.iroume@matech-cameroun.com>
Delivered-To: judicael.batchagnia@matech-cameroun.com
Received: from node32-ca.n0c.com
	by node32-ca.n0c.com with LMTP
	id KDKmGDh/T2rUHAkA9IX2vw
	(envelope-from <herve.iroume@matech-cameroun.com>)
	for <judicael.batchagnia@matech-cameroun.com>; Thu, 09 Jul 2026 11:00:08 +0000
Received: from 127.0.0.1 (unknown [10.123.3.49])
	by node32-ca.n0c.com (Postfix) with ESMTPA id 16A13859EB
	for <judicael.batchagnia@matech-cameroun.com>; Thu,  9 Jul 2026 11:00:08 +0000 (UTC)
DMARC-Filter: OpenDMARC Filter v1.4.1 node32-ca.n0c.com 16A13859EB
Authentication-Results: node32-ca.n0c.com; dmarc=fail (p=none dis=none) header.from=matech-cameroun.com
Authentication-Results: node32-ca.n0c.com; spf=fail smtp.mailfrom=matech-cameroun.com
DKIM-Filter: OpenDKIM Filter v2.11.0 node32-ca.n0c.com 16A13859EB
DKIM-Signature: v=1; a=rsa-sha256; c=relaxed/relaxed; d=matech-cameroun.com;
	s=default; t=1783594808;
	bh=YHmI9K96+xgxErr2Ko2aUHAMPrw0s3Doi5J2RicOLNA=;
	h=Date:From:To:Subject:In-Reply-To:References:From;
	b=a2ZeAdWfkScUPm0sfBTjksNo+R2gUi3+ET3nfPYJw9N84/t/BCU6yr7KXcfdf0iV3
	 IMot6yNwwati5npbnQvIawU6qZst3CCH0vzGF1gSrjG33iElEFUKBBGlu8ChF/song
	 vWV+nympT86+1O0k3S91GCe9sUGaXZnlcSYrRdSY=
MIME-Version: 1.0
Date: Thu, 09 Jul 2026 12:00:07 +0100
From: herve.iroume@matech-cameroun.com
To: judicael.batchagnia@matech-cameroun.com
Subject: Re: Fwd: Re: MAUVAISES VIDANGE OSSOSMBE
In-Reply-To: <dbacd32d5f34b26de04849c9e481bb6c@matech-cameroun.com>
References: <PAXPR05MB840034B6D20FA7D1850059C7F8FF2@PAXPR05MB8400.eurprd05.prod.outlook.com>
 <AMBPR05MB12867D93064099547C217F1669EFE2@AMBPR05MB12867.eurprd05.prod.outlook.com>
 <6102a4cad230c21a111d70663616f27c@matech-cameroun.com>
 <dbacd32d5f34b26de04849c9e481bb6c@matech-cameroun.com>
Message-ID: <66c09c30edfded2c1b386cd3ef42d482@matech-cameroun.com>
X-Sender: herve.iroume@matech-cameroun.com
X-Priority: 1 (Highest)
Content-Type: text/plain; charset=UTF-8;
 format=flowed
Content-Transfer-Encoding: 8bit

Le 2026-07-09 10:32, judicael.batchagnia@matech-cameroun.com a écrit :
> Bonjour Manager,
> Suite au stand up meeting de ce matin j'ai encore été interpelé par le
> RM IHS me demandant une fois plus de remplacer le technicien (PARKER
> TCHOUPE) de ce cluster de toute urgence  .
> 
> 
> Suggestion: Dans un premier temps pour calmer le climat qui prévôt en
> ce moment, je propose qu'il (PARKER TCHOUPE) prenne son congé annuel
> et à son retour de regagner un cluster à Yaoundé en tant que
> technicien second  afin de ne plus être aux feu de projecteur ,même si
> en réellement en interne nous savons qu'il est technicien .
> 
> 
> Bien cordialement
> 
> 
> 
> 
> 
> 
> Le 2026-07-09 09:44, judicael.batchagnia@matech-cameroun.com a écrit :
>> Bonjour Manager,
>> 
>> Ci-dessous les plaintes venant de IHS concernant le site OSSOMBE  "
>> Les mauvaises vidanges a répétition ont provoques une formation de
>> "patte collante" a l'intérieur du moteur (image en PJ), donc sur la
>> pompe a injection".  Tous nous sommes en copie de ces mails , j'ai
>> répondu en produisant les éléments de vidanges de ce générateur
>> ,étant donné que nous sommes en internes j'ai des questionnements et
>> remarques , nous avons les pompes à injection bloqués après
>> vidanges faudrait porter que nous portion une réflexion sur ce point
>> .
>> 
>>  		Site Name
>>  		Action Plan
>>  		Date de  dernier vidange
>>  		Issue
>>  		DATE DU ISSUE
>> 
>>  		ODZA MINKAN
>>  		Ge a vidange
>>  		20/06/2027
>>  		Injection Pump
>>  		27/06/2027
>> 
>>  		KOABANG EBOLMEDJOCK
>>  		Ge a vidange
>>  		29/07/2027
>>  		Injection Pump
>>  		01/07/2027
>> 
>>  		SOA TOWN
>>  		Ge a vidange
>>  		17/06/2027
>>  		Injection Pump
>>  		20/06/2027
>> 
>>  		OSSOMBE
>>  		Ge a vidange
>>  		03/07/2027
>>  		Injection Pump
>>  		07/07/2027 et le 08/07/2027
>> 
>>  		EKEKAM
>>  		Ge a vidange
>>  		30/06/2027
>>  		Injection Pump
>>  		07/07/2027
>> 
>> Bien cordialement
>> 
>> -------- Courriel original --------
>> Objet: Re: MAUVAISES VIDANGE OSSOSMBE
>> Date: 2026-07-09 07:19
>> De: "Alphonse K. Deufo" <alphonse.deufo@ihstowers.com>
>> À: Felix Bateu <felix.bateu@ihstowers.com>, Eko Mvondo Andre Patrick
>> <andre.eko@matech-cameroun.com>, Judicael Batchagnia
>> <judicael.batchagnia@matech-cameroun.com>, Jules Sagwa
>> <jules.sagwa@matech-cameroun.com>
>> Cc: 'Herve Iroume' <herve.iroume@matech-cameroun.com>, 'Amza Njatono'
>> <amza.njatono@matech-cameroun.com>, Bate Agbor
>> <bate.agbor@ihstowers.com>
>> 
>>  Hello @Jules Sagwa @Judicael Batchagnia
>>  Are you comfortable with this incident?
>> 
>>  Tenant Site ID
>>  Site ID
>>  IHS Site Name
>>  Cascaded Tenant Count
>>  Tenant Contract Site Priority
>>  IHS Site Power Topology
>>  Maintenance Vendor
>>  Outage Start Time
>>  Duration
>> 
>>  CTR_405
>>  IHS_YND_424
>>  Ossombe
>> 
>>  P4
>>  Hybrid-Gen
>>  MATECH CMR
>>  08/07/2026 12:37
>>  07:35:00
>> 
>>  T1259
>>  IHS_YND_424
>>  Ossombe
>>  7
>>  TIS
>>  Hybrid-Gen
>>  MATECH CMR
>>  08/07/2026 12:37
>>  07:35:00
>> 
>>  As a result, more than 7hours of outage two BTS and TX ( 09 sites)
>> 
>>  @Eko Mvondo Andre Patrick That's the result of just topping up the
>> oil instead of doing regular oil changes.
>> 
>>  Something need to be done
>> 
>>  Regards,
>> 
>>  Alphonse K. DEUFO
>> 
>>  Team Leader, Regional
>> 
>>  Mobile: +237 683661296
>> 
>>                 +237 658027928
>> 
>> -------------------------
>> 
>> From: Felix Bateu <felix.bateu@ihstowers.com>
>> Sent: Thursday, July 9, 2026 00:39
>> To: Eko Mvondo Andre Patrick <andre.eko@matech-cameroun.com>; Judicael
>> Batchagnia <judicael.batchagnia@matech-cameroun.com>; Jules Sagwa
>> <jules.sagwa@matech-cameroun.com>
>> Cc: Bate Agbor <bate.agbor@ihstowers.com>; Alphonse K. Deufo
>> <alphonse.deufo@ihstowers.com>
>> Subject: MAUVAISES VIDANGE OSSOSMBE
>> 
>> Bonjour a Tous
>> 
>> Apres l'incident d'OSSOMBE, le constat est clair.
>> 
>> Les mauvaises vidanges a repetition ont provoques une formation de
>> "patte colante" a l'interieur du moteur (image en PJ), donc sur la
>> pompe a injection.
>> 
>> Un vrai mecanicien doit absolument arrive dans ce site pour remplacer
>> la
>> pompe a injection et faire un lavage clomplet de l'interieur de ce
>> moteur.
>> 
>> Ce moteur ronfle tres mal.
>> 
>> Nous devons vite faire pour eviter le pire
>> 
>> Best Regarsds,
>> 
>> Felix Bateu
>> 
>> Officer, Sites
>> 
>> IHS Cameroon S.A.
>> 
>> 1602/1606, Blvd. de La Liberté, Akwa
>> 
>> P.O. Box 15115, Douala
>> 
>> Cameroon
>> 
>> www.ihstowers.com [1] [1 [2]]
>> 
>> Office :  +237 242738708
>> 
>> Mobile : +237 677549887
>> 
>>                  +237655999887
>> 
>> Skype: felix.bateu
>> 
>> Email: felix.bateu@ihstowers.com
>> 
>>  [2 [3]]
>> 
>>  [3 [4]]
>> 
>> Please consider the environment before printing this e-mail.
>> 
>> This email and its attachments, may contain confidential and/or
>> proprietary information, and could be used only by the person or
>> entity
>> to which it is addressed. If the reader of this e-mail is not the
>> intended recipient or his or her authorized agent, the reader is
>> hereby
>> notified that any disclosure of this e-mail is prohibited. If you have
>> received this e-mail in error, please notify the sender and delete it
>> from your system.
>> 
>> Links:
>> ------
>> [1] http://www.ihstowers.com/
>> [2] https://www.linkedin.com/company/2709806?trk=tyah
>> [3] https://www.youtube.com/user/ihstowers
>> 
>> Links:
>> ------
>> [1] http://www.ihstowers.com
>> [2] http://www.ihstowers.com/
>> [3] https://www.linkedin.com/company/2709806?trk=tyah
>> [4] https://www.youtube.com/user/ihstowers
Bonjour Félix Bateu.
Nous prenons avec un grand respect vos déclarations provenant du site de 
Ossombe.
Mais alors. Grande est notre surprise quand vous affirmer que se sont 
des mauvaises maintenances qui sont la résultante des pompes qui se 
bloquent.
Posez vous des bonnes questions.
Le groupe a combien d'heures de fonctionnement?
Dans nos fichiers, le groupe totalise un compteur horaire de 24116H.
La carte a été à : 18933h
La nouvelle carte est à :5683H
Les documents constructeur disent que la pompe doit fonctionner jusqu'à 
10000H, et les plus robustes vont jusqu'à 16000H.
D'où vient t'il donc que nous avons dépassé les plages de fonctionnement 
de la pompe . Et quand elle vse bloque , on parle de poor PM?
Si nous devons respecter le contrat, ce groupe est à remplacer.
Car il a plus de 24116H.
Avec un tel compteur , rien n'est plus sur.
Sauf si vous voulez chercher les poux sur une tête nue.
Nous demandons le remplacement de ce groupe vu son compteur horaire.
Suivant les clauses du contrat.
Bonne compréhension à tous.
Cordialement.
-- 
Jean Herve Iroume

DOA

herve.iroume@matech-cameroun.com

Tel:659 906 629

        697 335 400